SuperHot™ Boiler Treatment
Formulated Boiler Water Treatment
COMPLETE PROGRAM FOR SCALE AND CORROSION
SuperHot™ Boiler Treatment combines powerful scale and corrosion inhibitors with an oxygen scavenger to deliver full steam boiler protection. Polymer based inhibitors reduce scale and promote soft sludge that is easily removed through regular blowdown, keeping systems cleaner and running more efficiently.
REDUCES COSTS AND EXTENDS SYSTEM LIFE
SuperHot™ Boiler Treatment prevents energy robbing scale and controls oxygen corrosion to extend equipment life. Its concentrated formula reduces freight costs and minimizes empty container handling. This all in one solution improves efficiency, lowers maintenance demands, and protects your boiler system investment.
fed directly to the steam boiler. Use a State Industrial test kit to monitor sulfite levels daily. Feed product as needed to maintain a boiler sulfite level of 30 – 60 ppm. Also maintain the following control ranges:
Sulfite 30- 60 ppm Boiler TDS 3000 ppm max Hydrated alkalinity >200 ppm as OH P-alkalinity 300 – 500 Total alkalinity 700 ppm max Condensate pH 7.5 – 9.0
Blow Down: Blow down is a critical part of the scale control program for steam boiler systems. Perform bottom blow down as directed by your State Industrial sales professional to remove solids accumulations. Bottom blow down is required even if an automated surface blow down system is installed.
Condensate Treatment: Use State Superhot Steam Treatment to control corrosion in condensate return lines and receiver tanks. Follow label directions and maintain pH between 7.5 to 9.0.